GFE ORION 2/4/8 Zones - Orion Conventional Control Panel 2 - 8 Zone White

Not rated yet
0

Orion Control Panel

The Orion range of conventional control panels features three models with 2, 4 and 8 Zones of detection. Housed in a stylish modern ABS housing, the Orion is the ideal control panel for smaller installations.

Designed and manufactured to comply with the requirements of EN54 parts 2 and 4(1998) the Orion uses active End of Line monitoring to permit head removal protection as required by BS5839. (detector bases must be fitted with Diode)

Programmable Zone coincidence and alarm delay timer (0-10 min) are standard features to help reduce false alarms.

The one man test facility enables simple and rapid testing of the system at commissioning and during maintenance operations.

  • £197.80
  • excluding VAT
Qty:  

Orion Control Panel

The Orion conventional control panel range offers a creatively designed and visually pleasing solution for smaller cost-conscious projects demanding simplicity of operation. Versions available include 2, 4 and 8 zone panels and two styles of repeater.

The outstanding programmable features included in this panel range contradict the facilities commonly available in this type of panel and include: programmable time delay by zone, Day/Night mode, selectable non-latching zones and coincidence detection.

Operation is extremely intuitive, offering simple control and one-button disablement facilities, as well as the one man test mode which provides simple and efficient testing of the system.

Advanced configuration solutions include the following: a dedicated RS232 communication interface allowing connection of up to 4 remote repeater panels, addressable loop interface modules and multiplexed zonal output relays; giving one of the most highly advanced levels of system integration and compatibility existing on the market at this level.

 

Key Features 

  • 2, 4 and 8 zone non-expandable control panels
  • Up to 32 conventional smoke and/or heat detectors per zone
  • Active End of Line monitoring
  • Programmable non-latching zones
  • Delay timer programmable on/off per zone
  • Zone coincidence programmable for adjacent zones
  • Three Access Levels
  • One man test
  • Supervised auxiliary 24 volt output
  • 2 supervised/ monitored sounder circuits
  • 3 remote inputs used for activation of Class Change, Day/Night mode, and Reset
  • 2 Relay outputs fire and fault
  • Power supply 1,7A at 28V DC
  • Fully EN54 part 2 and 4 compliant
  • Repeater output
  • Multiplexed output for LEDs and additional relay outputs per zone (GFE-MPX-REL)
  • Addressable Loop Interface card (GFE-ADLI)

 

Please note, batteries are not included in the kit.  To see our range of batteries click here. 

TECHNICAL SPECIFICATIONS  
PRIMARY SUPPLY VOLTAGE- IN   230 +10% -15% V AC
PRIMARY SUPPLY VOLTAGE- OUT  28.5 V DC nominal
PRIMARY SUPPLY CURRENT-OUT     1.7 A @ 28.5 V DC nominal (max.)
SECONDARY SUPPLY VOLTAGE 21.0 min. - 27.2 max. V DC - BAT charger o/p 28 V DC
SECONDARY SUPPLY CURRENT OUTPUT 1.1 Amp Maximum @ 200C
INTERNAL BATTERY CAPACITY – MAXIMUM 2 x 12V x 7Ah Sealed VRLA Lead Acid Batteries
MAINS FUSE   4 A -250 V Slow Blow - 20 mm
BATTERY FUSE 1.6 Amp - Resettable
   
DETECTION CIRCUIT SPECIFICATION  
NUMBER OF CIRCUITS  2,4 or 8
ZONE CURRENT - QUIESCENT/ ALARM 4 mA / 60 mA - Maximum
MAX. CABLE RESISTANCE / CAPACITANCE 40 Ohms / 0.470 uF
END OF LINE MONITORING Active EOL - Capacitor
Bs5839 DETECTOR REMOVAL COMPLIANT YES provided diodes are fitted to detector base
DEVICES PER ZONE  32 Maximum - EN54 pt.2
ALARM RESISTANCE VALUE  270 - 1000 Ohms
SOUNDER CIRCUIT SPECIFICATION 2 - 500mA max. current drive per circuit - fully monitored
END OF LINE RESISTOR  27.5 V DC Nominal / 10 K Ohms - 1/4 Watt
   
 AUXILIARY OUTPUTS SPECIFICATION 
AUXILIARY RELAY OUTPUT 1 Fire (COM-NC-NO) - 1 Fault (COM-NC) non-supervised
RELAY CONTACT RATING 50 V DC - 1 Amp resistive loads
   
REMOTE INPUT SPECIFICATION 
EVACUATION (CC) - DAY/ NIGHT MODE Non-Latching - Voltage free contact
RESET      Non-Latching - Voltage free contact
   
MECHANICAL & OPERATING SPEC  
MAX. HUMIDITY 95% RH Non-Condensing
OPERATING TEMPERATURE -10ºC to 50ºC
WEIGHT          1.7 Kg - 7 Kg (inc. 2 x 7 AH 12 V bat.)
DIMENSIONS   272 (W) x 404 (H) x 107 (D) mm
    • Weight
      2.2500 kg
    • SKU
      764832260802
  • Brands
    Global Fire Equipment
  • Zones
    2, 4, 8
Customer reviews
There are no comments yet. Be the first to leave a comment
Please sign in to add review

Related products